ATSE for Industrial Plant Backup Power

Industrial changeover problems are usually motor problems. Where a plant board carries direct-on-line motors, the changeover must be specified around restart current and process priority, not only around the rated current of the board.

  • 01

    MOTE Electric ATSE equipment for industrial plants is tested to IEC 60947-6-1 and available from 100A to 3200A in PC class and CC class.

  • 02

    Adjustable transfer delays allow motor-heavy boards to be staged so restart current stays within generator capacity.

  • 03

    Plant incomer changeover is commonly supplied as an integrated switchgear assembly with metering and downstream distribution.

Industrial factory electrical control room with cabinet row and backup power changeover equipment
Step 1 — load classes

Which loads need changeover

Group the boards by the loads they serve, then read the tolerated interruption from the most sensitive load on that board.

Loads requiring changeover and their tolerated interruption
Loads requiring changeover and their tolerated interruption
LoadTolerated InterruptionNotes
Essential process control and PLC≤ 1 s (usually UPS supported)Small frame changeover at control board level
Critical pumps and compressors≤ 5 s – 15 sCheck restart current and soft-start arrangement
Production line drivesProcess dependentStaged restart preferred over simultaneous transfer
Workshop lighting and ventilation≤ 15 sEssential lighting board with 3P changeover
Utilities — water, effluent, air≤ 15 sMotor loads — verify generator step-load capability
Non-essential plantNot time criticalDeferred or manual transfer
Step 2 — configuration

Typical ATSE configuration

Ratings, poles, class and delay settings commonly used on each board type.

Typical ATSE configuration by plant board
Typical ATSE configuration by plant board
BoardCurrent RatingPolesClassTransfer Time Setting
Main plant incomer1000A – 1600A3P / 4PPC / CC1 s – 10 s
Process essential board400A – 800A3P / 4PPC / CC0.8 s – 5 s
Utilities board400A – 800A3PPC / CC0.8 s – 5 s
Control and instrument board100A – 320A2P / 3P / 4PCC0.5 s – 3 s
Step 3 — design notes

What to settle before the order

Size the changeover for restart, not only running current

Motor restart current can exceed running current several times over. Confirm the generator and the changeover device both accept the restart step before fixing the rating.

Stage the restart by process priority

Transferring a whole plant board at once can step the generator beyond its capacity. Set different delays so critical processes recover first.

Decide essential versus non-essential early

The split between essential and non-essential boards determines the changeover count and the generator rating more than any single device choice.

Related products

Products used on these boards

FAQ

Questions on this application

Why is motor restart current the key sizing input?

Because the changeover and the generator must both accept the restart step. Sizing on running current alone can produce a transfer that stalls the generator.

Can a plant use one ATSE for all loads?

It can, but staging by board is more common. Separate changeover on essential and utilities boards lets critical processes recover first without over-sizing the generator.

What is the typical transfer time for a plant sub-board?

Around 0.8 s to 5 s for essential boards, with longer settings where the process tolerates a longer interruption and generator capacity is tight.

Does MOTE Electric supply plant incomer assemblies?

Yes. Plant incomer changeover can be supplied as an integrated low voltage assembly with the ATSE, metering and downstream distribution.